top of page
Room Controller
Fancoil thermostat in high-quality design for individual single-room temperature- and fan control. A glass surface with intuitive touch control buttons and display combine design, feel and functionality in an outstanding way. The internal controller of the JOY calculates control values for fans and heating/cooling applications, which are provided via analog or digital outputs (depending on type). The possible integration of various external sensors (e.g. window contacts, change-over, condensation sensors, etc.) allows temperature and fan control tailored to the application. The device can be mounted in a standard flush-mounted box.
Technical Data
Radio technology | EnOcean (IEC 14543-3-10) 868 MHz, transmission power <10 mW |
Data transmission | 20 channels for sender, receiver or message-server, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | 0..+50 |
Output signal temperature | scaling according EEP, 0..+40 °C, 0..+50 °C |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±1 K (typ. at 21 °C), within default measuring range |
Measuring range humidity | 0..100% rH non-condensing |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Power supply | 24 V = (±10%) SELV, 24 V ~ (±10%) SELV, 85..260 V ~ |
Power consumption | typ. 2,5 W (24 V =), max. 2,5 VA (260 V ~), max. 3 VA (260 V ~) |
Display | LCD 60x44 mm, 240x160 px, backlight cold white |
Enclosure | PC, cover glass |
bottom of page